AM 900 V

690 m³/h at 30 dB(A) 
830 m³/h at 35 dB(A)

AM 900 V AM 900 V

AM 900 V is a local Air Handling Unit with high rate of heat recovery. The units is mounted on the floor and designed to work either using mixing ventilation or displacement ventilation, depending on the lay out and use of the room. AM 900 V is used in larger rooms like class rooms, conference rooms, and open offices where the need for efficient and silent air exchange has to be secured. It can be mounted on the floor either alone or integrated into a cupboard wall. The unit may be equipped with a modulating internal CO2-sensor that constantly monitors the CO2 content in the room air. This way the unit will deliver the exact amount of fresh air needed, no matter if the room is empty or occupied. The unit can be operated by using a Control Panel, or a digital BMS system.

Fields of application

  • Offices
  • Conference rooms
  • Schools and day-care centers
  • Modular buildings
     
Controlbox AQC P
Model V (Vertical intake/exhaust)
Version, inlet

M (Mixing)
D (Displacement)

Dimension (WxHxD)  M: 800x2323x588 mm
D: 800x2323x687 mm

 

Capacity, mixing at 30 dB(A)*
Capacity, mixing at 35 dB(A)*
Capacity, displacement at 30 dB(A)*
Capacity, displacement at 35 dB(A)*
Mixed, throw (0.2 m/s)*

Forced, adjacent zone (0.2 m/s)*

Nominal current*
Max. power consumption*
Electrical connection
Duct connection
Condensate drain
Weight
Heat exchanger
Supply air filter

Colour
Power cable
Leakage current
Dimensions (WxHxD)

Min. ceiling height
* Filter type, supply air / extract air: ePM10 75% / ePM10 75%


Electric heating surface (OPTION)
PREHEATER
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

Electric heating surface (OPTION)
COMFORT HEATER
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset
 

Water heating surface (OPTION)**
Max. operating temperature
Max. operating pressure
Heat output
Connection dimension
Materials pipes/fins
Open/close time, motor valve

** Mixed model only
*** Capacity at: supply/return temperature
60/40°C, water volume 33 l/h


Data sheets
Nomenclature

 

690 m³/h
830 m³/h
650 m³/h
800 m³/h
7.2 m. at 830 m³/h
6 m. at 690 m³/h
1.5 m. at 800 m³/h
1.2 m. at 650 m³/h
1.8 A
240 W
1 x 230 V + N + PE / 50 Hz
315 mm dia.
16 mm dia.
180 kg
3 x countercurrent (PET)
ePM10 75% (Option: ePM1 55% / ePM1 80%)
RAL 9010 (white)
1.5 mm²
< 6 mA
Mixed 800 x 2323 x 588 mm
Forced 800 x 2323 x 687 mm
2490 mm





1500 W
75°C
120°C
 


1050 W
75°C
120°C




90°C
10 bar
2345 W***
1/2" (DN 15)
Copper/aluminium
< 60 s
 

AM 900, Mixing

  AM 900
Viva controlpanel
Orbit controlpanel
Bypass
Electric preheater
Electric comfort heater
Water comfort heater
CO2 sensor (built-in)
PIR/motion sensor
Condensate pump
Motor-controlled exhaust damper
Motor-controlled main damper
Capacitive return for motorised damper
Countercurrent heat exchanger (PET)
Energy Meter


 

AM 900, Displacement 

  AM 900
Viva controlpanel
Orbit controlpanel
Bypass
Electric preheater
Electric comfort heater
Water comfort heater
CO2 sensor (built-in)
PIR/motion sensor (wall-mounted)
Condensate pump
Motor-controlled exhaust damper
Motor-controlled main damper
Capacitive return for motorised damper
Countercurrent heat exchanger (PET)
Energy Meter


Standard
Option

Calculate

Which unit to choose?

subscribe to our
newsletter

Do not miss out on important news within indoor climate, products and much more from Airmaster. Subscribe now!