AM 900 H

690 m³/h at 30 dB(A) 
830 m³/h at 35 dB(A)

AM 900 H AM 900 H

AM 900 H is a local Air Handling Unit with high rate of heat recovery. The units is mounted on the floor and designed to work either using mixing ventilation or displacement ventilation, depending on the lay out and use of the room. AM 900 H is used in larger rooms like class rooms, conference rooms, and open offices where the need for efficient and silent air exchange has to be secured. It can be mounted on the floor either alone or integrated into a cupboard wall. The unit may be equipped with a modulating internal CO2-sensor that constantly monitors the CO2 content in the room air. This way the unit will deliver the exact amount of fresh air needed, no matter if the room is empty or occupied. The unit can be operated by using a Control Panel, or a digital BMS system.

Fields of application

  • Offices
  • Conference rooms
  • Schools and day-care centers
  • Modular buildings

 

Controlbox AQC P
Model H (Horisontal intake/exhaust)
Version, inlet M (Mixing)
D (Displacement)
Dimension (WxHxD)   800x2323x588 mm

 

Capacity, mixing at 30 dB(A)*
Capacity, mixing at 35 dB(A)*
Capacity, displacement at 30 dB(A)*
Capacity, displacement at 35 dB(A)*
Mixed, throw (0.2 m/s)

Forced, adjacent zone (0.2 m/s)

Nominal current*
Max. power consumption*
Electrical connection
Duct connection
Condensate drain
Weight
Heat exchanger
Supply air filter

Colour
Power cable
Leakage current
Dimensions (WxHxD)

Min. ceiling height
* Filter type, supply air / extract air: ePM10 75% / ePM10 75%

Electric heating surface (OPTION)
PREHEATER
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

Electric heating surface (OPTION)
COMFORT HEATER
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset
 

Water heating surface (OPTION)**
Max. operating temperature
Max. operating pressure
Heat output
Connection dimension
Materials pipes/fins
Open/close time, motor valve

** Mixed model only
*** Capacity at: supply/return temperature
60/40°C, water volume 33 l/h


Data sheets 
Nomenclature 

 

 

690 m³/h
830 m³/h
650 m³/h
800 m³/h
7.2 m. at 830 m³/h
6 m. at 690 m³/h
1.5 m. at 800 m³/h
1.2 m. at 650 m³/h
1.8 A
240 W
1 x 230 V + N + PE / 50 Hz
315 mm dia.
16 mm dia.
180 kg
3 x countercurrent (PET)
ePM10 75% (Option: ePM1 55% / ePM1 80%)
RAL 9010 (white)
1.5 mm²
< 6 mA
Mixed 800 x 2323 x 588 mm
Forced 800 x 2323 x 687 mm
2490 mm





1500 W
75°C
120°C
 


1050 W
75°C
120°C



90°C
10 bar
2345 W***
1/2" (DN 15)
Copper/aluminium
< 60 s

AM 900, Mixing

    AM 900
Viva controlpanel  
Orbit controlpanel  
Bypass  
Electric preheater  
Electric comfort heater  
Water comfort heater  
CO2 sensor (built-in)  
PIR/motion sensor  
Condensate pump  
Motor-controlled exhaust damper  
Motor-controlled main damper  
Capacitive return for motorised damper  
Countercurrent heat exchanger (PET)  
Energy Meter  



AM 900, Displacement

    AM 900
Viva controlpanel  
Orbit controlpanel  
Bypass  
Electric preheater  
Electric comfort heater  
Water comfort heater  
CO2 sensor (built-in)  
PIR/motion sensor  
Condensate pump  
Motor-controlled exhaust damper  
Motor-controlled main damper  
Capacitive return for motorised damper  
Countercurrent heat exchanger (PET)  
Energy Meter  


Standard
Option

 

Calculate

Which unit to choose?

subscribe to our
newsletter

Do not miss out on important news within indoor climate, products and much more from Airmaster. Subscribe now!