AM 500 H

430 m³/h at 30 dB(A)
550 m³/h at 35 dB(A)

AM 500 H AM 500 H

AM 500 H is a local Air Handling Unit with high rate of heat recovery and is the perfect solution for middle size rooms. The unit secures the Indoor Air Quality in a responsible way also economically. The unit can be operated by using a Control Panel, or a digital BMS system.

Fields of application

  • Offices
  • Conference rooms
  • Schools and day-care centers
  • Modular buildings
     

 

Controlbox AQC L / AQC P
Model H (Horizontal intake/exhaust)
Version, inlet T (top)
C (center)
B (bottom)
Dimension (WxHxD)  1600x439x779 mm

Max. capacity at 30 dB(A)*
Max. capacity at 35 dB(A)*
Throw (0.2 m/s)*


Nominal current*
Max. power consumption*
Electrical connection
Duct connections
Condensate drain
Weight
Heat exchanger
Supply air filter

Colour
Power cable
Recommended fuse
Leakage current
Dimensions (WxHxD)
* Filter type, supply air / extract air: ePM10 75% / ePM10 75%

Electric heating surface (OPTION)
PREHEATER
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

COMFORT HEATER​
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

Water heating surface (OPTION)
Max. operating temperature
Max. operating pressure
Heat output
Connection dimension
Materials pipes/fins
Open/close time, motor valve

* Capacity at: supply/return temperature
60/40°C, water volume 25 l/h

Cooling module for AM 500 H
Nominal cooling capacity*
Min. cooling capacity*
Nominal EER
Max. airflow
Min. airflow**
Electricity supply
Nominal electrical output
Nominal current strength
Electrical output factor
Max. leakage current
Refrigerant
Filling
Duct connection
Drain hose, internal/external diameter.
Energy class (SEC class)
Weight
Dimensions (WxHxD)

* Measured according to EN308 and EN14825 at max. airflow with ePM10 75% filter.
** Cooling module activation.


Data sheets
Nomenclature
 

430 m³/h
550 m³/h
5 m. at 350 m³/h
5.9 m. at 450 m³/h
7.5 m. at 550 m³/h
1.1 A
132 W
1 x 230 V + N + PE / 50 Hz
Ø250 mm dia.
Ø16 mm dia.
108 kg
Countercurrent heat exchanger (alu)
ePM10 75% (Option: ePM1 55% / ePM1 80%)
Panels RAL 9010 (white)
1.5 mm²
10 A
< 6 mA
1600 x 439 x 779 mm




1000 W
75°C
120°C


630 W
75°C
120°C


90°C
10 bar
858 W
3/8" (DN 10)
Copper/aluminium
< 60 s






3280 W
820 W
3.16
500 m³/h
250 m³/h
1 x 230 V + AC / 50 Hz
1038 W
6.4 A
0.71
2.0 mA
R410a
480 g
250 mm dia.
8/12 mm dia.
A+
82,8 kg
1600 x 439 x 1185 mm

 

  AM 500 H
Viva controlpanel
Orbit controlpanel
Bypass
Electric preheating surface
Electric comfort heating surface
Water heating surface
CO2 sensor (wall-mounted)
CO2 sensor (built-in)
PIR/ motion sensor (wall-mounted)
PIR/ motion sensor (built-in) 
Hygrostat
Condensate pump
Cooling module
Motor-controlled exhaust damper
Motor-controlled main damper
Capacitive return for motorised damper
Countercurrent heat exchanger (aluminium)
Energy Meter
Wall-mounting frame
Ceiling-mounting frame
Mini B USB (on front of unit)

 
Standard
Option

Calculate

Which unit to choose?

subscribe to our
newsletter

Do not miss out on important news within indoor climate, products and much more from Airmaster. Subscribe now!