AM 1200 V

930 m³/h at 30 dB(A) 
1180 m³/h at 35 dB(A)

AM 1200 V AM 1200 V

AM 1200 V is a local Air Handling Unit where ventilation is combined with an elegant design and augmented functions allowing the unit to be integrated into the interior design of the room. AM 1200 V is a floor mounted unit with horizontal spigots. The unit can be placed against a wall (right-/left version) or as a room partitioner (center version). The surface for the unit is equipped with various types of design panels with different functions; Notice Boards, Mirrors, Acoustic panels, White Boards, Colored Panels – only the imagination is the limit. The unit can be operated by using a Control Panel, or a digital BMS system.

Panels

Variants



AM 1200 VRF2 (right, 2 open sides)
AM 1200 VRF3 (right, 3 open sides)
AM 1200 VCF3 (center, 3 open sides)
AM 1200 VCF4 (center, 4 open sides)
AM 1200 VLF2 (left, 2 open sides)
AM 1200 VLF3 (left, 3 open sides) 

Field of application

  • Offices
  • Conference rooms
  • Schools and day-care centers
  • Modular buildings

 

Controlbox AQC P
Model V (Vertical intake/exhaust)
Version, inlet Right
left
Center
Dimension (WxHxD)  496x2406x2427 mm

 

Capacity*:
Vertical model Ø400 mm
Right/left
Center
Vertical model Ø315 mm**
Right/left
Center

Throw (0.2 m/s)* - right/left

 

Throw (0.2 m/s)* - center

 


Nominal current*
Max. power consumption*
Electrical connection - with preheating surface
Duct connection
Condensate drain
Weight right/left
Weight center
Heat exchanger
Supply air filter

Leakage current
Dimensions (WxHxD)
* Filter type, supply air / extract air: ePM10 75% / ePM10 75%
** With roof cap module

Electric heating surface (OPTION)
PREHEATING SURFACE
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

Electric heating surface (OPTION)
COMFORT HEATING SURFACE
Heat output
Thermal circuit breaker, aut. reset
Thermal circuit breaker, man. reset

Water heating surface (OPTION)
Max. operating temperature
Max. operating pressure
Heat output
Connection dimension
Materials pipes/fins
Open/close time, motor valve

* Capacity at: supply/return temperature
60/40°C, water volume 72 l/h



Data sheets
Nomenclature

 

30 dB(A)

870 m³/h
980 m³/h

820 m³/h
920 m³/h
35 dB(A)

1130 m³/h
1260 m³/h

1060 m³/h
1170 m³/h


Min. 4 m. at 1000 m³/h
Max. 9 m. at 1000 m³/h
Min. 5.5 m. at 1300 m³/h
Max. 11 m. at 1300 m³/h
Min. 3 m. at 1000 m³/h
Max. 6.5 m. at 1000 m³/h
Min. 4 m. at 1300 m³/h
Max. 8 m. at 1300 m³/h

1.4 A (without/electric heating surface)
254 W
3 x 400 V + N + PE / 50 Hz

400 mm dia.
16 mm dia.
545 kg
630 kg
4 x countercurrent heat exchanger (alu)
ePM10 75% (Option: ePM1 55% / ePM1 80%)
< 9 mA
496 x 2406 x 2427 mm





2500 W
75°C
120°C
 


1670 W
75°C
120°C



90°C
10 bar
2454 W*
1/2" (DN 15)
Copper/aluminium
< 60 s

    AM 1200 V
Viva controlpanel  
Orbit controlpanel  
Bypass  
Electric preheating surface  
Electric comfort heating surface  
Water heating surface  
CO2 sensor (wall-mounted)  
CO2 sensor (built-in)  
PIR/motion sensor  
Hygrostat  
Condensate pump  
Spring-return motor on main damper (supply and return air side)  
Countercurrent heat exchanger (alu)  
Energy Meter  


Standard
Option

Calculate

Which unit to choose?

subscribe to our
newsletter